Signal is active with 1 mentions in latest observed window
Immediate actions
Patch affected systems immediately
Recommended action window: Monitor and triage in normal cycle
NVD description
Cleartext Storage of Sensitive Information vulnerability in Mitsubishi Electric GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric ICONICS Suite versions 10.97.3 and prior, Mitsubishi Electric MobileHMI versions 10.97.3 and prior, Mitsubishi Electric Hyper Historian versions 10.97.3 and prior, Mitsubishi Electric AnalytiX versions 10.97.3 and prior, Mitsubishi Electric GENESIS versions 11.02 and prior, Mitsubishi Electric MC Works64 all versions, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions ICONICS Suite versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions MobileHMI versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions Hyper Historian versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions AnalytiX versions 10.97.3 and prior, and Mitsubishi Electric Iconics Digital Solutions GENESIS versions 11.02 and prior allows a local attacker to disclose the SQL Server credentials stored in plaintext within the local SQLite file by exploiting this vulnerability, when the local caching feature using SQLite is enabled and SQL authentication is used for the SQL Server authentication. As a result, the unauthorized attacker could access the SQL Server and disclose, tamper with, or destroy data on the server, potentially cause a denial-of-service (DoS) condition on the system.
CVE-2025-14815 Cleartext Storage of Sensitive Information vulnerability in Mitsubishi Electric GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric ICONICS Suite versions 10.97… https://www.cve.org/CVERecord?id=CVE-2025-14815
Post summary
The post references CVE-2025-14815, describing it as a cleartext storage flaw in Mitsubishi Electric GENESIS64 and ICONICS Suite versions, but provides no exploit, mitigation, or active usage details.
The post lists three high‑severity CVEs with their CVSS scores and provides a generic link to a vulnerability portal, offering no further exploitation or mitigation details.
⚠️ **Vulnerability Alert:** CISA ICS Advisory: Mitsubishi Electric GENESIS64 and ICONICS Suite products (multiple ICS advisories/updates)
📅 **Timeline:** Disclosure: 2026-04-07, Patch: Multiple (see references)
🆔 **CVE-2025-14815** | 📊 CVSS: 8.8 (HIGH 🟠) | 📈 EPSS: Not Available
🆔 **CVE-2025-14816** | 📊 CVSS: 8.8 (HIGH 🟠) | 📈 EPSS: Not Available
🆔 **CVE-2025-7376** | 📊 CVSS: 5.9 (MEDIUM 🟡) | 📈 EPSS: 1.456%
🆔 **CVE-2025-0921** | 📊 CVSS: 6.5 (MEDIUM 🟡) | 📈 EPSS: 20.714%
🆔 **CVE-2024-8299** | 📊 CVSS: 7.8 (HIGH 🟠) | 📈 EPSS: 6.927%
🆔 **CVE-2024-8300** | 📊 CVSS: 7.0 (HIGH 🟠) | 📈 EPSS: 10.572%
🆔 **CVE-2024-9852** | 📊 CVSS: 7.8 (HIGH 🟠) | 📈 EPSS: 6.927%
🆔 **CVE-2023-2650** | 📊 CVSS: 3.7 (LOW 🟢) | 📈 EPSS: 99.698%
🆔 **CVE-2023-4807** | 📊 CVSS: 5.9 (MEDIUM 🟡) | 📈 EPSS: 74.338%
🆔 **CVE-2024-1182** | 📊 CVSS: 7.0 (HIGH 🟠) | 📈 EPSS: 18.210%
🆔 **CVE-2024-1573** | 📊 CVSS: 5.9 (MEDIUM 🟡) | 📈 EPSS: 47.466%
🆔 **CVE-2024-1574** | 📊 CVSS: 6.7 (MEDIUM 🟡) | 📈 EPSS: 34.105%
🛠️ **Exploit Maturity:** Not Available
📂 **Affected Versions:** GENESIS64/ICONICS Suite/MobileHMI/Hyper Historian/AnalytiX <=10.97.3, MC Works64 — all versions, GENESIS <=11.03 (varies by advisory), IoTWorX 10.95, GENESIS32/BizViz — various versions
🔧 **Fixed Versions:** GENESIS64/ICONICS Suite/MobileHMI/Hyper Historian/AnalytiX: 10.98+, GENESIS: 11.01 / 11.03+, IoTWorX: 10.96+, No fix for MC Works64/GENESIS32/BizViz — vendor mitigations
🫨 **Attack Vectors:**
- Local attacker / local access required
- Cleartext storage of SQL credentials in local SQLite cache and plaintext display in GUI
- Windows .LNK/symbolic-link exploitation enabling arbitrary writes
- DLL search-path/DLL planting (uncontrolled search path)
- OpenSSL parsing via BACnet Secure Connect (remote malformed cert/MAC)
- Authentication bypass via AD + automatic logon conditions
- Execution with unnecessary privileges / unsafe reflection
📝 **Summary:** Multiple local (and some remote) vulnerabilities across Mitsubishi/ICONICS ICS products expose plaintext SQL credentials, enable arbitrary file writes and DLL planting, and allow authentication bypass or unsafe code execution paths. Impacts include credential disclosure, tampering, denial-of-service, and, in some cases, elevated arbitrary code execution — patch immediately where available and apply mitigations for unpatchable products.
📈 **Impact Scope:** Affects multiple Mitsubishi Electric / ICONICS products used in critical manufacturing ICS: credential disclosure, information disclosure, arbitrary file tampering/deletion, DoS, and potential code execution with elevated privileges.
🛡️ **Recommended Actions:**
- Apply vendor-supplied patches immediately; isolate ICS networks, restrict remote/admin logins and enforce least privilege.
- Disable/delete local cache (C:\ProgramData\ICONICS\Cache\*.sdf and C:\ProgramData\ICONICS\11\Cache\*.sqlite3), prefer Windows auth for SQL Server, harden HHSplitter.exe, and follow vendor mitigations for unpatched products.
🪢 **Related Resources:**
- https://www.youtube.com/watch?v=KsZ6tROaVOQ
- https://en.wikipedia.org/wiki/2
🏷 **Tags:** #Cybersecurity#ICS#MitsubishiElectric
Post summary
The advisory announces multiple CVEs in Mitsubishi Electric and ICONICS products, lists CVSS scores, affected and fixed versions, outlines attack vectors, and recommends immediate patching and mitigation steps.
⚠️ **Vulnerability Alert:** Cleartext Storage and Display of SQL Server Credentials in Mitsubishi Electric GENESIS64 and ICONICS Suite (CVE-2025-14815, CVE-2025-14816)
🆔 **CVE-2025-14815** | 📊 CVSS: 8.8 (High 🟠) | 📈 EPSS: N/A%
🆔 **CVE-2025-14816** | 📊 CVSS: 8.8 (High 🟠) | 📈 EPSS: N/A%
🛠️ **Exploit Maturity:** Not Available
📂 **Affected Versions:** GENESIS64/ICONICS Suite/MobileHMI/Hyper Historian/AnalytiX <= 10.97.3, MC Works 64 (all versions), GENESIS <= 11.02
🔧 **Fixed Versions:** 10.98+ (GENESIS64/ICONICS Suite/MobileHMI/Hyper Historian/AnalytiX), 11.03+ (GENESIS), No fix planned (MC Works 64)
🫨 **Attack Vectors:**
- Local filesystem access to plaintext SQLite cache
- Local viewing/access to Hyper Historian Splitter GUI
- Requires SQL Server authentication to be enabled
- Insider or local attacker with file/GUI access
📝 **Summary:**
Two high-severity flaws expose SQL Server credentials in plaintext—one via local SQLite caching (CWE-312) and one via GUI display in Hyper Historian Splitter (CWE-317). An attacker with local or GUI access can steal those credentials to access, tamper with, or destroy database data and move laterally.
📈 **Impact Scope:** Plaintext SQL credentials enable unauthorized DB access leading to data disclosure, tampering, destruction, service disruption, and potential lateral movement.
🛡️ **Recommended Actions:**
- Apply vendor fixes: upgrade to 10.98+ for GENESIS64/ICONICS Suite/MobileHMI/Hyper Historian/AnalytiX or 11.03+ for GENESIS
- If patching isn't immediate, disable local SQLite caching and Hyper Historian Splitter or restrict access to them
- Enforce least-privilege access to filesystem and GUIs; prefer integrated/Windows authentication over SQL auth
- Rotate exposed SQL credentials and monitor for anomalous local and DB activity
🪢 **Related Resources:**
- https://www.cisa.gov/news-events/ics-advisories/icsa-26-097-01
- https://www.mitsubishielectric.co.jp/psirt/vulnerability/pdf/2025-023.pdf
🏷 **Tags:** #Cybersecurity#ICS#MitsubishiElectric
Post summary
The post announces two high‑severity CVEs in Mitsubishi Electric software, detailing their technical aspects and providing explicit patch and mitigation guidance.
⚠️ **Vulnerability Alert:** Plaintext storage of sensitive information in multiple Mitsubishi Electric products (CVE-2025-14815, CVE-2025-14816)
🆔 **CVE-2025-14815**
🆔 **CVE-2025-14816**
🛠️ **Exploit Maturity:** Not Available
📂 **Affected Versions:** GENESIS64/ICONICS Suite/MobileHMI/Hyper Historian/AnalytiX ≤10.97.3, GENESIS ≤11.02, MC Works64: All versions
🔧 **Fixed Versions:** Patched/latest versions for GENESIS64/ICONICS/MobileHMI/Hyper Historian/AnalytiX/GENESIS, No fix for MC Works64 (vendor recommends replacement or mitigations)
🫨 **Attack Vectors:**
- Local access to machines with enabled local SQLite cache allowing reading of plaintext SQL credentials
- Access to Hyper Historian Splitter GUI/plaintext GUI storage to obtain SQL credentials
- Use of obtained SQL Server credentials to access/modify databases leading to disclosure, tampering, or DoS
📝 **Summary:**
Multiple Mitsubishi Electric products store SQL Server credentials in plaintext (local SQLite cache and Hyper Historian Splitter), allowing attackers who obtain those credentials to access or tamper with databases and disrupt services. MC Works64 currently has no vendor fix and requires replacement or mitigations.
📈 **Impact Scope:** Plaintext SQL credential exposure across affected GENESIS/ICONICS products may enable unauthorized DB access, data disclosure, tampering, and service disruption; MC Works64 has no available fix.
🛡️ **Recommended Actions:**
- Apply vendor-provided updates/patches where available
- Replace MC Works64 with GENESIS64 or apply vendor-provided mitigations/workarounds
- Rotate SQL Server credentials if exposure is suspected
- Audit for use of local SQLite cache and Hyper Historian Splitter and remediate plaintext credential storage
- Harden access to systems storing credentials and monitor for unauthorized access
🪢 **Related Resources:**
- https://jvn.jp/vu/JVNVU90646130/
🏷 **Tags:** #Cybersecurity#MitsubishiElectric#ICS
Post summary
Plaintext SQL Server credentials are stored in Mitsubishi Electric GENESIS/ICONICS products. Patches are available for most affected versions, but MC Works64 has no fix, requiring replacement or mitigation.